Taylor Power® TD1000 Details
Purpose Built Standby-Diesel Generators

Capacity:

Rated: 1000 kW
Category: Stationary
Sub Group: Standby-Diesel

Engine:

Make: Mitsubishi
Model: S12H-Y2PTAW-1
Fuel Type: Diesel

Alternator:

Please refer to spec sheet for your particular model

Unit Features:

  • Heavy Duty Steel Base
  • Vibration Isolators
  • Oil Drain Valve with Extension
  • Battery Rack & Cables
  • High Ambient Unit Mounted Radiator
  • Battery Charging Alternator
  • Factory Powder Coating
  • Factory Test
  • Owner's Manual

Description:

Taylor Power standby diesel generators have been ETL Certified to UL2200. Depending upon your specific requirements, Taylor Power provides standby generators ranging from 9kW to 2000kW. The TD1000 is rated at 1000kW and has many optional features to meet the unique needs of the individual customers. For more information on this generator, please refer to our specification sheet.

Output Power Options:

Diesel OUTPUT POWER OPTIONS:

Output Power Options 125°C RISE STANDBY RATING 105°C RISE CONTINUOUS RATING sKVA
Make Voltage Alternator Phase Hertz kW/kVA Amps kW/kVA Amps 30% Voltage Dip
Marathon 600 741RSS4282 3 60 1000/1250 1204 920/1150 1108 1550
Marathon 277/480 741RSL4045 3 60 1000/1250 1505 920/1150 1385 2600
Marathon 120/208 741RSL4045 3 60 1000/1250 3474 920/1150 3196 2600
Marathon 120/240 741RSL4045 3 60 1000/1250 3011 920/1150 2770 2600
Marathon 277/480 742RSL4049 3 60 1020/1275 1535 925/1156 1392 3110
Marathon 120/208 742RSL4049 3 60 1020/1275 3543 925/1156 3213 2260
Marathon 120/240 742RSL4049 3 60 1020/1275 3071 925/1156 2785 2260
Stamford 600 HCI634J07 3 60 1000/1250 1204 920/1150 1108 3000
Stamford 277/480 HCI634J311 3 60 1000/1250 1505 920/1150 1385 3080
Stamford 120/208 HCI634J311 3 60 920/1150 3196 850/1063 2953 2330
Stamford 120/240 HCI634J311 3 60 920/1151 2770 131/164 2559 2330