Taylor Power® TD2000 Details
Purpose Built Standby-Diesel Generators

Capacity:

Rated: 2000 kW
Category: Stationary
Sub Group: Standby-Diesel

Engine:

Make: Mitsubishi
Model: S16R-Y2PTAW2-1
Fuel Type: Diesel

Alternator:

Please refer to spec sheet for your particular model

Unit Features:

  • Heavy Duty Steel Base
  • Vibration Isolators
  • Oil Drain Valve with Extension
  • Battery Rack & Cables
  • High Ambient Unit Mounted Radiator
  • Battery Charging Alternator
  • Factory Powder Coating
  • Factory Test
  • Owner's Manual

Description:

Taylor Power standby diesel generators have been ETL Certified to UL2200. Depending upon your specific requirements, Taylor Power provides standby generators ranging from 9kW to 2000kW. The TD2000 is rated at 2000kW and has many optional features to meet the unique needs of the individual customers. For more information on this generator, please refer to our specification sheet.

Output Power Options:

Diesel OUTPUT POWER OPTIONS:

Output Power Options 125°C RISE STANDBY RATING 105°C RISE CONTINUOUS RATING sKVA
Make Voltage Alternator Phase Hertz kW/kVA Amps kW/kVA Amps 30% Voltage Dip
Marathon 600 744RSS4293 3 60 2000/2500 2408 1790/2238 2156 3600
Marathon 277/480 744RSL4054 3 60 2000/2500 3011 1790/2238 2694 5800
Marathon 120/208 744RSL4054 3 60 1840/2300 3196 1680/2100 2918 5800
Marathon 120/240 744RSL4054 3 60 1590/1988 3023 1590/1988 3023 5800
Marathon 277/480 744RSL4056 3 60 2000/2500 3011 1820/2275 2740 5800
Marathon 120/208 744RSL4056 3 60 1950/2438 3387 1780/2225 3092 5800
Marathon 120/240 744RSL4056 3 60 1790/2238 3404 1650/2063 3137 5800
Stamford 600 PI734F07 3 60 2000/2500 2408 1790/2238 2156 6500
Stamford 277/480 PI734F312 3 60 2000/2500 3011 1790/2238 2694 6600
Stamford 120/208 PI734F312 3 60 1876/2345 3258 1752/2190 3043 4450
Stamford 120/240 PI734F312 3 60 1616/2020 3073 1504/1880 2860 3250