Taylor Power® TG350 Details
Purpose Built Standby-NG/LP Generators

Capacity:

Rated: 350 kW
Category: Stationary
Sub Group: Standby-NG/LP

Engine:

Make: Doosan
Model: 18.3L
Fuel Type: NG/LP

Alternator:

Please refer to spec sheet for your particular model

Unit Features:

  • Heavy Duty Steel Base
  • Vibration Isolators
  • Oil Drain Valve with Extension
  • Battery Rack & Cables
  • High Ambient Unit Mounted Radiator
  • Battery Charging Alternator
  • Factory Powder Coating
  • Factory Test
  • Owner's Manual

Description:

Taylor Power standby Natural Gas (NG) / Liquid Propane (LP) generators have been ETL Certified to UL2200. Depending upon your specific requirements, Taylor Power provides standby NG/LP generators ranging from 30kW to 450kW. The TG350 is rated at 350kW and has many optional features to meet the unique needs of the individual customers. For more information on this generator, please refer to our specification sheet.

Output Power Options:

NG/LP STANDBY OUTPUT POWER OPTIONS:

LP Output Power Options NATURAL GAS
125°C RISE STANDBY RATING
LP VAPOR
125°C RISE STANDBY RATING
sKVA
Make Voltage Alternator Phase Hertz kW/kVA Amps kW/kVA Amps 30% Voltage Dip
Marathon 600 433PSL6248 3 60 350/438 421 240/300 289 1380
Marathon 277/480 433CSL6216 3 60 350/438 527 240/300 361 1424
Marathon 120/208 433CSL6216 3 60 350/438 1216 240/300 834 1069
Marathon 120/240 433CSL6216 3 60 350/438 1054 240/300 723 1069
Marathon 120/240 433CSL6216 1 60 241/241 1004 240/240 1000 430
Marathon 277/480 433CSL6220 3 60 355/444 534 255/319 384 1469
Marathon 120/208 433CSL6220 3 60 355/444 1233 255/319 886 1103
Marathon 120/240 433CSL6220 3 60 355/444 1069 255/319 768 1103
Marathon 120/240 433CSL6220 1 60 241/241 1004 240/240 1000 430
Stamford 600 HCI434F17 3 60 350/438 421 240/300 289 1250
Stamford 277/480 HCI434F311 3 60 350/438 527 240/300 361 1265
Stamford 120/208 HCI434F311 3 60 350/438 1216 240/300 834 980
Stamford 120/240 HCI434F311 3 60 350/438 1054 240/300 723 980
Stamford 120/240 HCI434F311 1 60 230/230 958 230/230 958 670

NG/LP CONTINOUS OUTPUT POWER OPTIONS:

LP Output Power Options NATURAL GAS
125°C RISE CONTINOUS RATING
LP VAPOR
125°C RISE CONTINOUS RATING
sKVA
Make Voltage Alternator Phase Hertz kW/kVA Amps kW/kVA Amps 30% Voltage Dip
Marathon 600 433PSL6248 3 60 350/438 421 240/300 289 1380
Marathon 277/480 433CSL6216 3 60 350/438 527 240/300 361 1424
Marathon 120/208 433CSL6216 3 60 350/438 1216 240/300 834 1069
Marathon 120/240 433CSL6216 3 60 350/438 1054 240/300 723 1069
Marathon 120/240 433CSL6216 1 60 241/241 1004 240/240 1000 430
Marathon 277/480 433CSL6220 3 60 355/444 534 255/319 384 1469
Marathon 120/208 433CSL6220 3 60 355/444 1233 255/319 886 1103
Marathon 120/240 433CSL6220 3 60 355/444 1069 255/319 768 1103
Marathon 120/240 433CSL6220 1 60 241/241 1004 240/240 1000 430
Stamford 600 HCI434F17 3 60 350/438 421 240/300 289 1250
Stamford 277/480 HCI434F311 3 60 350/438 527 240/300 361 1265
Stamford 120/208 HCI434F311 3 60 350/438 1216 240/300 834 980
Stamford 120/240 HCI434F311 3 60 350/438 1054 240/300 723 980
Stamford 120/240 HCI434F311 1 60 230/230 958 230/230 958 670