Taylor Power® TG40 Details
Purpose Built Standby-NG/LP Generators

Capacity:

Rated: 40 kW
Category: Stationary
Sub Group: Standby-NG/LP

Engine:

Make: GM
Model: 4.3L
Fuel Type: NG/LP

Alternator:

Please refer to spec sheet for your particular model

Unit Features:

  • Heavy Duty Steel Base
  • Vibration Isolators
  • Oil Drain Valve with Extension
  • Battery Rack & Cables
  • High Ambient Unit Mounted Radiator
  • Battery Charging Alternator
  • Factory Powder Coating
  • Factory Test
  • Owner's Manual

Description:

Taylor Power standby Natural Gas (NG) / Liquid Propane (LP) generators have been ETL Certified to UL2200. Depending upon your specific requirements, Taylor Power provides standby NG/LP generators ranging from 30kW to 450kW. The TG40 is rated at 40kW and has many optional features to meet the unique needs of the individual customers. For more information on this generator, please refer to our specification sheet.

Output Power Options:

NG/LP STANDBY OUTPUT POWER OPTIONS:

LP Output Power Options NATURAL GAS
125°C RISE STANDBY RATING
LP VAPOR
125°C RISE STANDBY RATING
sKVA
Make Voltage Alternator Phase Hertz kW/kVA Amps kW/kVA Amps 30% Voltage Dip
Marathon 600 361PSL1632 3 60 40/50 48 40/50 48 154
Marathon 277/480 361CSL1600 3 60 40/50 60 40/50 60 154
Marathon 120/208 361CSL1600 3 60 40/50 139 40/50 139 116
Marathon 120/240 361CSL1600 3 60 40/50 120 40/50 120 116
Marathon 120/240 361CSL1600 1 60 39/39 163 39/39 163 53
Marathon 120/240 361CSL1611 1 60 40/40 167 40/40 167 75
Marathon 277/480 361CSL1601 3 60 40/50 60 40/50 60 189
Marathon 120/208 361CSL1601 3 60 40/50 139 40/50 139 142
Marathon 120/240 361CSL1601 3 60 40/50 120 40/50 120 142
Marathon 120/240 361CSL1601 1 60 40/40 167 40/40 167 63
Stamford 600 UCI224D17 3 60 40/50 48 40/50 48 195
Stamford 277/480 UCI224D311 3 60 40/50 60 40/50 60 182
Stamford 120/208 UCI224D311 3 60 40/50 139 40/50 139 136
Stamford 120/240 UCI224D311 3 60 40/50 120 40/50 120 136
Stamford 120/240 UCI224D311 1 60 40/40 167 40/40 167 96
Stamford 120/240 PI1144J06 1 60 40/40 167 40/40 167 65

NG/LP CONTINOUS OUTPUT POWER OPTIONS:

LP Output Power Options NATURAL GAS
125°C RISE CONTINOUS RATING
LP VAPOR
125°C RISE CONTINOUS RATING
sKVA
Make Voltage Alternator Phase Hertz kW/kVA Amps kW/kVA Amps 30% Voltage Dip
Marathon 600 361PSL1632 3 60 40/50 48 40/50 48 154
Marathon 277/480 361CSL1600 3 60 40/50 60 40/50 60 154
Marathon 120/208 361CSL1600 3 60 40/50 139 40/50 139 116
Marathon 120/240 361CSL1600 3 60 40/50 120 40/50 120 116
Marathon 120/240 361CSL1600 1 60 39/39 163 39/39 163 53
Marathon 120/240 361CSL1611 1 60 40/40 167 40/40 167 75
Marathon 277/480 361CSL1601 3 60 40/50 60 40/50 60 189
Marathon 120/208 361CSL1601 3 60 40/50 139 40/50 139 142
Marathon 120/240 361CSL1601 3 60 40/50 120 40/50 120 142
Marathon 120/240 361CSL1601 1 60 40/40 167 40/40 167 63
Stamford 600 UCI224D17 3 60 40/50 48 40/50 48 195
Stamford 277/480 UCI224D311 3 60 40/50 60 40/50 60 182
Stamford 120/208 UCI224D311 3 60 40/50 139 40/50 139 136
Stamford 120/240 UCI224D311 3 60 40/50 120 40/50 120 136
Stamford 120/240 UCI224D311 1 60 40/40 167 40/40 167 96
Stamford 120/240 PI1144J06 1 60 40/40 167 40/40 167 65